eCite Digital Repository
Parametric study and optimization of a full-scale converter transformer winding
Citation
Tan, Y and Yu, X and Ji, S and Zang, Y and Wang, X, Parametric study and optimization of a full-scale converter transformer winding, International Journal of Heat and Mass Transfer, 181 Article 121861. ISSN 0017-9310 (2021) [Refereed Article]
Copyright Statement
© 2021 Elsevier
DOI: doi:10.1016/j.ijheatmasstransfer.2021.121861
Abstract
Thermal and hydraulic performance of the converter transformer winding is essential for improving the reliability and economy of the oil-cooled converter transformer. In this paper, a full-scale axisymmetric numerical heat transfer model was developed for a unilateral valve winding of an oil-cooled converter transformer. This model was first validated using data from the reference. Effects of the oil inlet/outlet position and the block washer number on the oil velocity and disc temperature of the winding were then studied under different oil mass flow rates. The thermal, hydraulic and comprehensive performance of the winding was investigated using Colburn-j factor (j), Darcy friction factor (f) and JF factor (JF), respectively. Finally, the optimal oil inlet/outlet position and block washer number were identified and the performance of the winding in the optimized design was further evaluated. The results showed that both the oil inlet/outlet position and block washer number had a significant impact on the disc temperature of the winding. The number of overheated discs was reduced by 50% when the oil inlet was set near the outside wall of the winding, compared with the conventional design in which the oil inlet was set at the middle of the winding. Furthermore, the maximum and mean temperature rises of the winding were reduced and the comprehensive performance was improved by setting the block washers. The optimal design for the winding was that the oil inlet was allocated near the outside wall of the winding, the number of the block washer was 3 and the oil mass flow rate was 2mo. In this optimal design, the maximum and mean temperature rises of the winding were reduced by 56.1% and 63.9%, respectively, and the comprehensive performance was improved by 145%, compared with the conventional design.
Item Details
Item Type: | Refereed Article |
---|---|
Keywords: | converter winding, heat transfer, Colburn-j factor, thermal performance, JF factor |
Research Division: | Engineering |
Research Group: | Mechanical engineering |
Research Field: | Numerical modelling and mechanical characterisation |
Objective Division: | Energy |
Objective Group: | Energy storage, distribution and supply |
Objective Field: | Energy services and utilities |
UTAS Author: | Wang, X (Professor Xiaolin Wang) |
ID Code: | 146167 |
Year Published: | 2021 |
Web of Science® Times Cited: | 1 |
Deposited By: | Engineering |
Deposited On: | 2021-08-24 |
Last Modified: | 2021-11-25 |
Downloads: | 0 |
Repository Staff Only: item control page